Sale!

ABB RTD0003 RTD Input Module

Original price was: $1,068.00.Current price is: $1,000.00.

Parameter Value
Manufacturer ABB
Product Type RTD Input Module
Catalog Designation RTD0003
Compatible Hardware ABB Relion Series (e.g., REM620, numerical protection IEDs)
Slot Location Typically designated for slot X105 (verify with specific IED manual)
Category: SKU: RTD0003 Tag:

Description

The ABB RTD0003 is a specialized plug-in hardware module designed primarily for use within ABB’s Relion protection and control relay families (such as the REM620 motor protection IEDs). It provides precise temperature monitoring capabilities via Resistance Temperature Detectors (RTDs) to protect critical electrical assets like motor windings, transformers, and bearings from thermal overload.

 

Supply Status and Commercial Terms

  • Condition: New Surplus / Factory Sealed
  • Availability: In stock for immediate dispatch
  • Standard Warranty: 12 months from date of shipment
  • Lead Time: 1 to 2 business days for standard dispatch
  • Pricing Note: Listed price is indicative. Price subject to market conditions; contact us for a firm quote.

 

Technical Specifications

Parameter Value
Manufacturer ABB
Product Type RTD Input Module
Catalog Designation RTD0003
Compatible Hardware ABB Relion Series (e.g., REM620, numerical protection IEDs)
Slot Location Typically designated for slot X105 (verify with specific IED manual)
Input Types Pt100, Pt250, Ni100, Cu10profil, Ni125 (verify with OEM datasheet)
Measurement Channels Multiple differential channels (exact count depends on host IED configuration)
Isolation Galvanically isolated from internal IED circuitry
Operating Temperature -25 to +55 °C (housing limits apply)
Conformity / Standards IEC 60255, CE, cULus (verify with OEM datasheet)

 

Engineering and Field Deployment Notes

When integrating the RTD0003 module into existing protection IEDs during retrofits or new panel builds, adhere to standard instrumentation practices to ensure measurement accuracy.

Integration and Compatibility

  • Slot Allocation: Ensure the host IED has the physical slot available (commonly slot X105 on REM620 units). Inserting or removing option modules must be done with auxiliary control power de-energized to prevent internal bus errors.
  • Sensor Shielding: Use twisted, shielded pair cables for all field-run RTD inputs. Ground the shield at one end only (typically the panel ground bar) to minimize electromagnetic interference (EMI) from adjacent medium-voltage VFD cables or high-current busbars.
  • Configuration Tooling: The host IED must be configured using ABB PCM600 (Protection and Control IED Manager) to map the physical inputs of the RTD0003 to internal thermal protection logic, alarms, and trip matrices.

 

Frequently Asked Questions

Which ABB protection relays support the RTD0003 module?

It is primarily utilized within the ABB Relion modular protection and control product lines, such as the REM620 motor management relays. Always check the specific ordering code and hardware compatibility list of your base IED.

Does the module supply excitation current for the RTDs?

Yes, the module provides the necessary constant current source excitation required to measure resistance changes across Pt100 or equivalent elements without introducing self-heating measurement errors.

What configuration software is required to enable the module?

You must use ABB PCM600 to configure the hardware parameters, set alarm/trip thresholds for temperature monitoring, and assign logical outputs.

ABB DI890 (3BSE040134R1) S800 High Integrity Intrinsic Safety Digital Input Module
ABB DIS880 (3BSE078768R1) System 800xA Select I/O Safety Digital Input SCM
ABB PM864AK01 (3BSE018161R1) Original Controller Unit
ABB PFEA113-20 (3BSE0210058RD20) Tension Electronics
ABB GFD233A 3BHE022294R0101 – Gate Firing Driver Module