TRICONEX 3700 | 24 V DC backplane | 32-channel differential DC-coupled TMR analog input module

$14,850.00

  • Product Model: 3700
  • Brand: TRICONEX
  • Warranty: One Year
  • Input Voltage: 24 V DC backplane
  • Operating Temperature: 0°C to +60°C​
  • Storage Temperature: -40°C to +85°C
  • Condition: New/Used
    In Stock: In Stock
    Delivery Time: 3-5 days
    HS Code: 8443919090.00

Description

Technical Specifications

  • Product Model: 3700
  • Brand: TRICONEX
  • Warranty: One Year
  • Input Voltage: 24 V DC backplane
  • Operating Temperature: 0°C to +60°C​
  • Storage Temperature: -40°C to +85°C
  • Response Time: 55 ms input update rate​
  • Protection Class: IP20
  • Accuracy Class: <0.15% of FSR (0° to 60°C)​
  • Output Frequency: N/A (analog input)
  • Rated Current Range: 0-20 mA (250 Ω shunt); 0-5 VDC
  • Communication Interface: Tricon backplane; requires External Termination Panel (ETP)
  • Supported Protocols: TMR mid-value selection voting​
  • Overload Capacity: 150 VDC/115 VAC continuous protection​
  • Dimensions: 39 × 1.5 × 37 cm; ≈2 kg​

Product Overview

The TRICONEX 3700 is a 32-channel differential DC-coupled TMR analog input module for Tricon safety systems, converting 0-5 VDC or 0-20 mA field signals from transmitters into three independent digital values for mid-value selection voting. It solves measurement integrity challenges in ESD, HIPPS, and process control by providing three isolated A/D converters per point, ensuring accurate data despite single-channel failures. Process engineers in oil & gas, refining, and power benefit from its high common-mode rejection (-80 dB DC-100 Hz), 30 MΩ input impedance, and continuous diagnostics covering each channel. Requiring ETP panels for field termination, the 3700 supports hot-spare replacement while maintaining SIL 3 loops. With 12-bit resolution and <0.15% accuracy across 0-60°C, it delivers reliable pressure, temperature, level, and flow data essential for safety-critical decisions in harsh industrial environments. (159 words)

 

Key Functions

 

Triple Independent A/D Conversion

Three separate analog-to-digital converters process each input point simultaneously, feeding mid-value selection to main processors. Single converter failure doesn’t affect voted output accuracy.​

High Common-Mode Rejection

-80 dB rejection (DC-100 Hz) eliminates ground potential differences and noise coupling between channels. Maintains signal integrity in shared ground cabinets.​

 

 

Application Scenarios

Safety Transmitter Arrays

Refineries consolidate 32 pressure transmitters into single 3700 cards feeding ESD logic; TMR voting rejects single transmitter drift while diagnostics flag failing loops.​

Turbine Monitoring

Power plants read bearing temperatures and vibration signals; common-mode rejection filters motor noise while three-channel processing prevents spurious trips from pickup failure.​

HIPPS Pressure Sensing

Gas plants monitor high-pressure headers; 55 ms update rate keeps protection logic current while overrange protection handles proof-test spikes without damage.​

Distillation Column Control

Petrochemical units track multiple tray temperatures; hot-spare capability allows card replacement during turnarounds without losing column safety envelope monitoring.

 