Sale!

Fireye 95DSS2E-1CG InSight I | UL/FM Approved / 2.50 kg / Factory Sealed

Original price was: $3,322.00.Current price is: $3,200.00.

Parameter Value
Device Type Integrated Microprocessor-Based Flame Scanner (InSight I Series)
Detector Configuration Dual Detector (Ultraviolet [UV] and Infrared [IR])
Spectral Response Range Broad-spectrum UV/IR discrimination capability
Electrical Connections 10-lead flying lead configuration with integrated cable gland
Output Signals Self-checking shutter output, flame relay contact, and 4-20 mA analog flame intensity
Operating Temperature Range -40 °C to +70 °C (-40 °F to +158 °F optical housing limits)
Category: SKU: 95DSS2E-1CG Tag:

Description

1. Unboxing & Physical Snapshot

  • Model & Brand: Fireye / InSight I Series Integrated Flame Scanner (Part No. 95DSS2E-1CG)
  • Physical Dimensions (Approximate W x H x D): Cylindrical optical barrel housing, approx. 76.0 mm diameter x 254.0 mm length (\varnothing 3.0 \times 10.0 in).
  • Estimated Shipping Weight: 2.50 kg (5.51 lbs).
  • What’s in the Box: Dual detector (IR and UV) flame scanner assembly, integrated 10-lead wiring harness connection with cable gland, internal signal processing board, optical sight-pipe alignment collar, and manufacturer compliance documentation.

 

2. Product Introduction

Industrial utility boilers, large commercial burners, and heavy-duty process heaters require highly reliable flame monitoring systems to ensure safe combustion control and prevent catastrophic fuel accumulation hazards. This Fireye InSight I integrated flame scanner combines both ultraviolet (UV) and infrared (IR) detection technologies into a single optical housing—which is vital for discriminating between true burner flames and background furnace radiation across changing fuel conditions.

The ruggedized, weather-tight aluminum enclosure protects sensitive internal microprocessors and optical sensors from ambient burner deck heat, dust, and vibration. Translating live flame flicker frequencies into discrete relay closures and 4-20 mA analogue output signals, this hardware maintains strict burner management safety compliance under continuous industrial operation.

 

3. Core Technical Specifications

Parameter Value
Device Type Integrated Microprocessor-Based Flame Scanner (InSight I Series)
Detector Configuration Dual Detector (Ultraviolet [UV] and Infrared [IR])
Spectral Response Range Broad-spectrum UV/IR discrimination capability
Electrical Connections 10-lead flying lead configuration with integrated cable gland
Output Signals Self-checking shutter output, flame relay contact, and 4-20 mA analog flame intensity
Operating Temperature Range -40 °C to +70 °C (-40 °F to +158 °F optical housing limits)
Enclosure Protection Class NEMA 4X / IP66 weatherproof and dust-tight housing classification
Power Supply Requirements 24 V DC nominal operating voltage

 

4. Global Compliance & Industry Certifications

  • Expected Regulatory Approvals: CE Approved, UL Listed (UL 372 / UL 1998), FM Global (Factory Mutual) Approved, CSA, and industrial burner safety standards compliance (NFPA 85).
  • Safety & Compliance Impact: Compliance with strict FM and UL burner management standards guarantees that fail-safe internal shutter mechanisms and self-checking circuits shut down fuel valves instantly upon optical path loss, safeguarding high-capacity combustion systems.
  • Verify specific lot certifications with OEM.

 

5. Long-Term Storage & Asset Preservation Guide

Keep this flame scanner sealed inside its original anti-static and moisture-barrier packaging to protect internal circuit boards from electrostatic discharge events. Crucial Maintenance Note: Protect the optical glass lens assembly with its factory cap during storage to prevent scratching or dust accumulation. Maintain warehouse storage conditions at a relative humidity level strictly below 60% and temperatures between -20 °C and +60 °C.

 

6. Physical Installation Prerequisites

  • Verify that the burner mounting sight pipe is clean, properly aligned, and provides an unobstructed view of the primary combustion zone prior to scanner insertion.
  • Ensure purge air is connected and maintained at the designated pressure to keep the optical lens clean from soot, fly ash, and high furnace temperatures.
  • Route low-voltage signal leads and analog output cables completely away from high-voltage ignition transformer wiring to prevent electromagnetic interference.

 

7. Buyer’s FAQ (Logistics & Compliance Focus)

  • Q: What Harmonized System (HS) code applies for international customs clearance on this Fireye flame scanner?
    • A: Industrial combustion safety controls, flame monitors, and optical sensing apparatus typically classify under HS code 8531.10 or 9031.80. Confirm local code accuracy with your trade compliance broker.
  • Q: Does this specific model include integrated wiring leads?
    • A: Yes. The “-1CG” designation signifies a configuration supplied with 10 leads and an integrated cable gland for direct field wiring termination.
  • Q: How does the Country of Origin (COO) documentation affect our import compliance audit?
    • A: Manufacturing origin records correspond to authorized global production facilities within Fireye’s combustion safety division. Check commercial invoice documentation for precise country details to satisfy trade treaty requirements.
  • Q: Is specialized transit insurance recommended during shipment?
    • A: Yes. Because precision optical flame scanners contain delicate internal lenses, electronic shutters, and microprocessors, comprehensive transit insurance guarding against mechanical shock and vibration is strongly advised.