Sale!

Honeywell Safety Manager FC-SAI-1620M Safety Analog Input Module

Original price was: $16,500.00.Current price is: $16,000.00.

Parameter Specification / Value
Module Type Safety Analog Input (SAI) Module
Model Designation FC-SAI-1620M
Number of Channels 16 input channels, galvanically isolated
Input Signal Range 0 to 20 mA or 4 to 20 mA DC
A/D Conversion Resolution 16-bit internal resolution
Accuracy \le \pm 0.1\% of full scale baseline at 25 °C
Category: SKU: Honeywell FC-SAI-1620M Tag:

Description

The Honeywell FC-SAI-1620M is a high-reliability, safety-certified analog input module designed for integration within the Safety Manager and Safety Manager SC architectures. Featuring 16 isolated channels, this module interfaces directly with 0–20 mA and 4–20 mA field transmitters, such as pressure, temperature, and flow sensors.

Engineered for use in critical process safeguarding environments, the module supports applications requiring high integrity, including Emergency Shutdown (ESD) systems, Fire and Gas (F&G) monitoring, and Burner Management Systems (BMS), maintaining certification up to SIL 3 (IEC 61508).

 

Commercial Availability & Procurement

Logistics Parameter Status & Details
Product Condition New Original (Factory Sealed / New Surplus) or Refurbished (Fully certified and dynamically load-tested via factory diagnostic rigs)
Warranty 12-month comprehensive industrial warranty
Availability Available in global surplus stock; standard industrial packaging and dispatch within 24 to 48 hours
Pricing Note Pricing fluctuates based on current regional allocation and critical facility turn-around demands. Contact our Honeywell process safety division for an itemized quotation.

 

Technical Specifications

Parameter Specification / Value
Module Type Safety Analog Input (SAI) Module
Model Designation FC-SAI-1620M
Number of Channels 16 input channels, galvanically isolated
Input Signal Range 0 to 20 mA or 4 to 20 mA DC
A/D Conversion Resolution 16-bit internal resolution
Accuracy \le \pm 0.1\% of full scale baseline at 25 °C
Module Supply Voltage 24 VDC redundant via chassis backplane power bus
Safety Integrity Level Certified up to SIL 3 (IEC 61508) and PL e (EN ISO 13849-1)
PCB Protective Layer Conformal coated (“M” suffix variant) for harsh G3 atmospheric compliance
Operating Temperature −5 to +60 °C (+23 to +140 °F)

 

Functional Architecture & Transmitter Wiring

The FC-SAI-1620M incorporates an onboard microprocessor that runs continuous self-diagnostic sweeps in the background. It samples analog input signals through an A/D converter matrix while verifying loop current and checking for ground faults.

 [ 4-20mA Field Transmitter ] ──► [ FTA Terminal Block ] ──► [ FC-SAI-1620M Module ]
                                                                       │
                                                            (Onboard 16-Bit A/D)
                                                                       │
                                                                       ▼
                                                          [ Redundant Controller Bus ] 

Field Termination Assemblies (FTA)

Field connections do not land directly on the FC-SAI-1620M module housing. Instead, they route through high-density system cables to a matching Field Termination Assembly (FTA) board mounted on a DIN rail within the marshalling panel. The FTA provides the physical screw terminals, loop current fusing, and optional 24 VDC transmitter power distribution.

Critical Field Note: The “M” suffix in the model number designates that the printed circuit board assembly has received a factory conformal coating. This protective layer isolates sensitive semiconductor traces from airborne contaminants, conductive dust, and corrosive moisture, making the FC-SAI-1620M essential for installation in highly demanding areas such as offshore platforms, wastewater treatment spaces, and chemical processing facilities.

 

Field Replacement & Redundancy Management

In high-availability configurations, the Honeywell Safety Manager utilizes redundant pairs of FC-SAI-1620M modules placed side-by-side in the I/O chassis. If an internal board component fails on the primary card, control bumplessly shifts to the secondary module without tripping the active safety loop.

Hot-Swapping Procedure

  1. Verify that the redundant companion module’s green RUN or OK LED is illuminated solid, indicating it is healthy and carrying the active process load.
  2. Put on an approved ESD grounding wrist strap and clamp its lead to an unpainted, grounded section of the cabinet frame.
  3. Loosen the upper and lower captive extraction screws on the defective FC-SAI-1620M module front panel.
  4. Swing the extraction handles outward to unseat the module from the backplane connectors, and slide the card straight out along its guide tracks.
  5. Inspect the replacement module’s rear connector pins for alignment, push it firmly into the slot until the handles lock, and tighten the retention fasteners.
  6. Observe the front display matrix; the card will perform its self-test and automatically sync its parameter configuration with the active controller.

 

Frequently Asked Questions

Q: Why does a specific channel report a “Line Monitoring Fault” or flag an analog low saturation alarm?

A line monitoring fault indicates that the current loop has drifted outside normal operating boundaries (\le 3.6 mA or \ge 21.0 mA). This behavior is typically caused by a broken field wire (open circuit), a shorted transmitter loop, or a field sensor component failure. Inspect the loop current on the corresponding FTA channel using a digital multimeter.

Q: Does the FC-SAI-1620M module directly support HART communication pass-through?

The base FC-SAI-1620M module strips off high-frequency elements to optimize safety tracking loops and does not natively pass digital HART telemetry to the asset management system. For setups requiring integrated HART diagnostics alongside SIL 3 protection loops, Honeywell provides specific HART-compatible analog input modules or dedicated FTA termination blocks equipped with external analog filters.

Q: What is the primary indicator of a fatal internal card hardware failure?

The front plate contains a dedicated red I/O Fault or ERR indicator LED. If this light illuminates solid red while the green RUN LED goes dark, the internal safety watchdog has detected a critical internal error, such as a faulty A/D converter or memory corruption. When this occurs, the module automatically isolates its input stages from the system bus to prevent corrupted data from affecting the main safety processor.

Honeywell 05701-A-0302 Single-Channel Control Card
Honeywell 05704-A-0144 System 57 Quad Control Card