Description
The Honeywell 05704-A-0144 is a four-channel (Quad) control card designed for the System 57 rack-mounted gas detection platform. This module accepts inputs from up to four independent gas detectors—including catalytic pellistor sensors, electrochemical cells, or 4–20 mA transmitters—and provides centralized monitoring, display, and alarm functions. By consolidating four channels onto a single card, the 05704-A-0144 increases cabinet density and reduces the hardware footprint in large-scale industrial gas monitoring installations.
Commercial and Availability Status
-
Condition: New Original (Factory Sealed)
-
Warranty: 12-Month Mechanical and Electrical Warranty
-
Availability: In Stock
-
Lead Time: Ships within 1 to 2 business days
-
Pricing Note: Price is subject to market availability; contact our technical procurement team for a firm, project-specific quote.
Technical Specifications
| Parameter | Specification / Value |
| Model Number | 05704-A-0144 |
| Series | Honeywell Analytics System 57 |
| Card Type | Quad Channel Control Card (4-Channel) |
| Input Types | Catalytic Bridge, Electrochemical, or 4–20 mA |
| Power Supply | 18 to 32 V DC |
| Power Consumption | 3.5 W typical (excluding sensor power) |
| Display Type | Multi-segment LCD per channel with backlight |
| Alarm Thresholds | 3 levels per channel (A1, A2, A3) + Fault |
| Output Signals | Individual 4–20 mA analog output per channel |
| Relay Outputs | Common Alarms (A1, A2, A3) + Individual Channel Faults |
| Operating Temperature | −5 to +55 °C (+23 to +131 °F) |
| Mounting | Standard System 57 3U Rack |
Operational Architecture and Interface
The 05704-A-0144 serves as the interface between the hazardous area gas sensors and the facility’s safety logic or SCADA system.
Multi-Channel LCD Display
The front panel of the card features a high-contrast LCD that provides real-time gas concentration readings, engineering units (e.g., %LEL, ppm, %Vol), and channel status indicators. The display cycles through the four channels or can be locked to a specific channel during calibration.
Signal Processing and Alarm Logic
Each of the four channels operates independently. The card’s internal firmware evaluates incoming signals against three user-definable alarm setpoints.
-
Rising/Falling Alarms: Configurable for oxygen deficiency (falling) or toxic/combustible gas (rising).
-
Latching/Non-Latching: Alarms can be set to clear automatically or require manual reset once gas levels subside.
-
Time Delay: Adjustable on-delay prevents nuisance alarms caused by momentary signal spikes or transient interference.
Engineering and Maintenance Guidelines
1. Sensor Configuration and Calibration
The 05704-A-0144 is commissioned using the Honeywell Engineering Interface Software or via the front-panel tactile buttons. During commissioning, you must select the correct sensor drive current (for catalytic sensors) or input range (for 4–20 mA transmitters).
Field Maintenance Note: When performing a “Bump Test” or full calibration on a sensor connected to the Quad Card, the specific channel must be placed in Inhibit Mode. This prevents the 4–20 mA output and common alarm relays from triggering the plant’s emergency shutdown (ESD) systems during the test.
2. Backplane Compatibility
The 05704-A-0144 requires a specific System 57 Quad Channel Interface Backplane (e.g., 05704-A-0121 or similar). The card cannot be used in slots designed for the 05701 single-channel cards due to the increased pin density required for four independent signal loops.
3. Relay Mapping
While the card provides common alarm relays via the backplane, additional individual channel relay expansion is possible using the 05704-A-0145 relay card. This is critical for applications where each gas detector must trigger a localized beacon or sounder.
Frequently Asked Questions
Can I mix different gas types on a single 05704-A-0144 card?
Yes. Each of the four channels is independently configurable. For example, Channel 1 can be set for %LEL Methane (Catalytic), Channel 2 for H2S (Electrochemical), and Channels 3 and 4 for CO2 (4–20 mA Infrared).
What does a “Fault” indication on the LCD signify?
A fault code typically indicates a loop integrity issue. This could be a “Sensor Under-range” (often caused by sensor drift or negative zero shift), a “Sensor Open Circuit,” or an internal hardware failure on the card itself. Check the terminal voltage at the backplane to isolate the issue between the field wiring and the control card.
Is the 05704-A-0144 compatible with the older System 57 racks?
The Quad Card is compatible with the standard 19-inch System 57 rack frame, but it requires the 05704-series quad-channel backplane. If you are upgrading an older rack that used 05701 single-channel cards, the backplane must be replaced to accommodate the 05704-A-0144.