Sale!

Honeywell 04230-A-1001 SHC-1 Handheld Interrogator

Original price was: $22,000.00.Current price is: $20,000.00.

Parameter Value
Brand / Manufacturer Honeywell Analytics (Legacy Zellweger)
Part Number / MPN 04230-A-1001
Model / Type Designation SHC-1
Software Baseline Version 4V0 embedded firmware
Compatible Detectors Searchpoint Optima, Searchpoint Optima Plus, Searchline Excel
Category: SKU: 04230-A-1001 Tag:

Description

The Honeywell 04230-A-1001 (Type SHC-1) is an intrinsically safe, portable maintenance, configuration, and calibration tool designed for Honeywell Analytics fixed infrared gas detection systems. Running factory-installed 4V0 software, this device serves as the primary field interface for commissioning, interrogating, and diagnostic troubleshooting of Searchpoint Optima, Searchpoint Optima Plus, and Searchline Excel gas detectors. It establishes a digital link with field devices to read operational metrics, execute zero/span calibrations, and download event logs without taking the detectors offline.

 

Technical Specifications

Parameter Value
Brand / Manufacturer Honeywell Analytics (Legacy Zellweger)
Part Number / MPN 04230-A-1001
Model / Type Designation SHC-1
Software Baseline Version 4V0 embedded firmware
Compatible Detectors Searchpoint Optima, Searchpoint Optima Plus, Searchline Excel
Communication Interface Digital RS-485 serial link
Enclosure Material Stainless Steel ANSI 316 / Impact-resistant composite
Hazardous Area Certification ATEX Certified (Intrinsically Safe for Zone 1 and Zone 2)
Operating Temperature 0 °C to +40 °C (DMT Evaluated structural envelope: −25 °C to +55 °C)
Operating Humidity 0 to 99% RH (Non-condensing)
Net Weight 0.5 kg (1.1 lbs)

 

Supply Status and Procurement Logic

  • Condition: New Original / Factory Sealed (New Surplus units occasionally cycled into active rotation)
  • Warranty: 12-Month Comprehensive Technical Warranty
  • Availability: Active allocation via safety and instrumentation logistics pipelines
  • Lead Time: Ships within 1 to 3 business days from order processing
  • Pricing: Variable based on international safety component indices. Contact our engineering desk for a firm, contract-specific quote.

 

Critical Field Integration Rules & Constraints

When using the SHC-1 interrogator on live processing plants, maintenance teams must strictly observe the following constraints to prevent loop failures or code errors:

Certification and Isolation Boundaries

The ATEX intrinsic safety (IS) certification of the 04230-A-1001 interrogator is strictly conditional. It only maintains its safety rating when connected via an approved isolation junction. You must never splice the interrogator lines directly into a bare, non-isolated 24 V DC power loop. Field connection must proceed exclusively via the IS socket on a DVC100 / DX100 termination unit or by deploying the specialized 04230-A-1025 SHC Protection Device module with its factory flying leads.

Regional Certification Variances

The part number 04230-A-1001 is the ATEX-approved model. If your plant operates under alternative regulatory regimes, this exact part number cannot be used as a generic substitute. For projects requiring North American approvals, you must source regional variants: 2104B2351 for UL certification boundaries or 2104B2354 for CSA-regulated jurisdictions.

Firmware-Level Interoperability

The 4V0 software suite embedded within this unit is optimized for the internal register maps of Searchpoint Optima Plus and Searchline Excel cross-duct units. When servicing legacy, non-Plus Searchpoint Optima units, certain advanced extended diagnostic sub-menus may report a null read or communication timeout error. This is an inherent software architecture boundary, not a hardware defect; verify individual detector register maps before executing field-wide parameter alterations.

 

Frequently Asked Questions (FAQ)

What occurs if the interrogator display screen shows a “No Communication” error upon connection?

Verify that the RS-485 lines are clean and the DVC100/DX100 IS socket pins are free of oxidation. This error usually stems from a baud rate mismatch between the detector’s multi-drop network address configuration and the default interrogation scan routine of the 4V0 software. If the gas detector is actively starting up, wait 2 minutes for its internal diagnostic routine to clear before initiating an interrogation sweep.

Can a zero or span calibration be performed in a classified area using this device?

Yes, because the 04230-A-1001 is certified as intrinsically safe, it allows maintenance technicians to perform full sensor trim, zero calibration, and span alignment directly at the point of detection within a classified hazardous area without requiring a hot work permit.

Is it necessary to recalibrate the interrogator unit itself?

No. The SHC-1 is an electronic interface device that transmits configuration commands and views data registers from the detector; it contains no internal gas-sensing cells. Calibration adjustments are written directly into the non-volatile memory of the target Searchpoint Optima Plus or Searchline Excel device rather than the handheld tool itself. Ensure the unit’s housing seals remain intact to preserve moisture isolation.

Honeywell 05701-A-0302 Single-Channel Control Card
Honeywell 05704-A-0144 System 57 Quad Control Card
Honeywell FC-QPP-0002 – Quad Processor Pack
Honeywell CC-PWRR01 – Redundant Power Supply Module