Description
The Bently Nevada 330101-00-28-90-02-00 is a standard 3300 XL 8 mm proximity probe designed for continuous vibration and displacement monitoring on fluid-film bearing machinery. It utilizes eddy-current transducer principles to measure both static (shaft position) and dynamic (vibration) parameters relative to a conductive target.
Procurement and Availability
- Availability: Typically stocked by specialized automation distributors; factory-allocated builds may apply for specific project quantities
- Standard Lead Time: 3 to 5 business days for stock items; 8 to 10 weeks if factory production is required
- Warranty: 12-month standard replacement warranty from invoice date
- Condition: Factory New / Original Surplus
- Pricing Notice: Listed price is indicative and subject to market fluctuations. Contact our sales desk for a formal quotation.
Technical Specifications
| Parameter | Value |
| Manufacturer | Bently Nevada (Baker Hughes) |
| Product Part Number | 330101-00-28-90-02-00 |
| Product Series | 3300 XL 8 mm Proximity Transducer System |
| Thread Configuration (Option) | 3/8-24 UNF (without armor) |
| Unthreaded Length (Option) | 0.0 inches (00) |
| Overall Case Length (Option) | 2.8 inches (28) |
| Total Length (Option) | 9.0 meters (29.5 feet) (90) |
| Connector and Cable Type (Option) | Miniature coaxial ClickLoc connector with standard cable (02) |
| Agency Approvals (Option) | Not required (00) |
| Linear Range | 2.0 mm (80 mils), spanning from 0.25 mm to 2.3 mm |
| Incremental Scale Factor | 7.87 mV/µm (200 mV/mil) nominal |
| Operating Temperature | -35 to +177°C (-31 to +350°F) for probe tip |
| Storage Temperature | -51 to +177°C (-60 to +350°F) |
| Pull Strength (CableLoc) | 330 N (75 lbf) maximum pull strength between probe tip and cable |
Engineering and Integration Context
When deploying or replacing proximity probes like the 330101-00-28-90-02-00 in turbomachinery applications, strict mechanical and electrical guidelines must be observed.
- System Matching: The 3300 XL system relies on calibrated component matching. Ensure that the extension cable and Proximitor sensor are calibrated for the exact system length (9.0 meters total system length in this configuration) to maintain measurement linearity and frequency response.
- Mounting and Gapping: The probe requires a minimum shaft diameter of 50.8 mm (2.0 inches) and a minimum flat target size of 15.2 mm (0.6 inches) to prevent edge effects. Use a digital multimeter or Bently Nevada test kit to verify the initial set-point voltage (typically -10 V DC nominal within the linear operating range) during gapping.
- Connector Handling: ClickLoc connectors feature a specialized locking mechanism that produces an audible click. Hand-tighten these connections to ensure proper electrical continuity, and protect exposed connectors from moisture and oil ingress using heat-shrink tubing or rated environmental boots if installed in harsh areas.
Frequently Asked Questions
Q: Can this 9.0-meter probe be used directly with a Proximitor sensor without an extension cable?
A: No. The total system length option (90 designates 9.0 meters) incorporates the matched electrical length of the probe cable combined with an extension cable to reach the Proximitor sensor. Component lengths must sum correctly to match the specific Proximitor sensor calibration (typically 5-meter or 9-meter total system configurations).
Q: Does changing the probe length require recalibrating the monitoring system?
A: The 3300 XL design allows complete interchangeability of system components without individual bench calibration, provided the total system length (probe plus extension cable) matches the Proximitor sensor calibration type (e.g., 9-meter systems). Always verify system rev tags and rack configuration settings.