Parameter Value
Manufacturer Rockwell Automation / Allen-Bradley
Module Type FLEX I/O Analog Output Module
Catalog Number 1794-OE4
Number of Channels 4 Analog Outputs (single-ended)
Category: SKU: 1794-OE4 Tag:

Description

The Allen-Bradley 1794-OE4 is a 4-channel analog output module designed for the FLEX I/O distributed automation platform. It converts 12-bit digital values from a network adapter (such as EtherNet/IP, ControlNet, or PROFIBUS adapters) into isolated analog current (4 to 20 mA) or voltage (\pm 10 V, 0 to 10 V) signals. These outputs drive field-level actuators, positioning valves, control dampers, and variable frequency drive (VFD) speed references.

 

Commercial Availability & Terms

  • Condition: New Original (Factory Sealed), New Surplus, or Refurbished (Fully Bench Tested on automated test profiles) available.
  • Warranty: 12-Month Functional Warranty across all product conditions.
  • Lead Time: Typically ships from stock within 1 to 2 business days.
  • Pricing Note: List pricing fluctuates based on supply dynamics and product series updates (Series A vs. Series B). Contact our industrial procurement desk for a firm, formal quote.

 

Technical Specifications

The following electrical and environmental specifications define the operational limits of the 1794-OE4 module.

Parameter Value
Manufacturer Rockwell Automation / Allen-Bradley
Module Type FLEX I/O Analog Output Module
Catalog Number 1794-OE4
Number of Channels 4 Analog Outputs (single-ended)
Output Current Ranges 4 to 20 mA, 0 to 20 mA (Configurable)
Output Voltage Ranges \pm 10 V, 0 to 10 V (Configurable)
Digital Resolution 12-bit binary (all ranges)

• Voltage: 2.56 mV/count

• Current: 5.13 \muA/count

Data Format Left-justified, 2’s complement or binary
External Power Input 24 V DC Nominal (20.4 to 31.2 V DC range)
FlexBus Current Draw 20 mA maximum at 5 V DC
Isolation Voltage Channel-to-system: 850 V DC for 1 second

Channel-to-channel: None

Maximum Output Load • Current loop: 750\ \Omega at 24 V DC

• Voltage loop: \ge 1000\ \Omega resistive

Compatible Terminal Bases 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN
Operating Temperature 0 to +55^\circC (+32 to +131^\circF)

 

Field Integration & Terminal Mapping

1. Terminal Base Wiring Layout

The 1794-OE4 requires a separate terminal base unit (e.g., 1794-TB3) for direct field wire landings. Analog output signals and their specific returns are assigned sequentially across the base rows. External 24 V DC loop power must be wired to designated terminals to energize the internal digital-to-analog converter (DAC) drive circuits.

2. Configuration Profiles and Scaling

Output ranges are established via the configuration registers inside the controller’s programming environment (RSLogix 5000 / Studio 5000 Logix Designer). The output channels map to specific words in the module’s output image array. If the external 24 V DC auxiliary supply drops below the lower operating threshold (20.4 V DC), a bit is pulled in the module input status register indicating a “power low” fault condition.

3. Noise Mitigation Rules

Because this module is single-ended (sharing a common internal analog return), ground loops can distort target signal metrics.

  • Utilize shielded twisted-pair cables for all analog runs.
  • Ground the cable shield at the terminal base chassis ground bar only.
  • Maintain physical separation between analog signal conductors and high-voltage AC motor control lines to avoid electromagnetic interference.

System Constraint: The 1794-OE4 does not support hot-swapping (“Removal and Insertion Under Power” or RIUP) if installed on older legacy terminal bases or if the process environment poses an explosive hazard. Disconnect all field-side power before servicing the hardware card.

 

Frequently Asked Questions

Can I mix voltage and current outputs on the same 1794-OE4 module?

Yes. Each channel can be configured independently via the controller software profile. For instance, Channel 0 can be mapped for a 4 to 20 mA output to drive a valve positioner, while Channel 1 can output 0 to 10 V to command a fan motor drive reference.

What is the mechanical difference between the Series A and Series B versions?

Series B modules include updated internal electronic components to manage component obsolescence and offer improved immunity against high-frequency electrical noise. Series B units are fully backwards compatible with existing Series A application slots and utilize identical terminal bases.

What causes an output channel to clip or lag its commanded target value?

The most common causes are a field load impedance exceeding the maximum 750\ \Omega specification on current loops, or a voltage drop in the external 24 V DC power input supply lines. Measure the voltage across the terminal base power inputs under full load conditions

Allen-Bradley 1756-PA72 ControlLogix AC Power Supply
Allen-Bradley 1761-L32AWA MicroLogix 1000 Controller
Allen-Bradley 2094-BC02-M02-S – Kinetix 6000 Multi-Axis Servo Drive
Allen-Bradley 1756-IF8 – ControlLogix Analog Input Module