Description
During a recent control panel migration at a municipal wastewater treatment plant in Ohio, the site installation team encountered intermittent processor drops whenever large aeration pumps cycled on. Swapping out the aging power supply for a new Allen-Bradley 1756-PA72 eliminated these voltage sag disruptions immediately. This standard AC power supply mounts directly into the left side of any 1756 ControlLogix chassis, providing regulated DC power backplane currents to support processors, I/O modules, and network communication cards.
Are you looking to replace an active system power supply or stock critical spares for a planned facility shutdown? On-machine operational data confirms that this unit maintains output stability even during momentary line-voltage fluctuations.
Global Logistics, Availability, and Warranty Terms
Procuring core industrial infrastructure components internationally requires transparent supply chain management to maintain plant operational timelines.
-
Product Condition: New Original, Factory Sealed in original Allen-Bradley packaging.
-
Stock Availability: Stocked at regional logistics hubs for immediate worldwide dispatch.
-
Standard Lead Time: Processes and ships within 1 to 2 business days via international air express.
-
Warranty Period: Fully covered by a 12-month industrial replacement warranty from the invoice date.
-
International Pricing Note: The listed price functions as a baseline market reference. Final transaction pricing varies according to global stock fluctuations, regional distribution costs, and contract tiers. Contact our trade office for an official pro forma quote.
Technical Specifications: Allen-Bradley 1756-PA72
The physical capacity and electrical tolerances of this power supply are determined by its internal transformer and regulator design. Verify these backplane current limits against your current RSLogix 5000 / Studio 5000 chassis layout calculation before installation.
| Parameter | Value / Specification |
| Product Line | ControlLogix 1756 System |
| Input Voltage Range | 85 to 265 V AC (Auto-Ranging), Single-Phase |
| Operating Frequency | 47 to 63 Hz |
| Max. Power Consumption | 100 VA (Volt-Amperes) |
| Max. Power Output | 75 W @ 0 to +60°C |
| Backplane Current Capacity |
1.5 A @ 1.2 V DC
4 A @ 3.3 V DC
13 A @ 5.1 V DC
2.8 A @ 24 V DC |
| Isolation Voltage | 250 V (continuous), reinforced insulation type |
| Mounting Location | Left side of 1756-A4, -A7, -A10, -A13, or -A16 chassis |
| Conductor Screw Torque | 0.8 N·m (7 lb·in) on terminal block screws |
Field Implementation and Backplane Current Loading
The 1756-PA72 uses an integrated circuit design that translates standard line voltage into four distinct DC rails across the chassis backplane. Physical installation is straightforward: the module slides into the dedicated slot on the far left of the chassis until the top and bottom plastic tabs click into place, securing its backplane connectors without a separate cable harness.
Well, technically the power supply can provide up to 13 A on the 5.1 V DC rail, but its overall output is capped at a total power draw of 75 W. In our field deployments, we always run a power budget verification inside Rockwell’s Integrated Architecture Builder (IAB) software prior to commissioning large 16-slot chassis packed with high-density analog modules or Ethernet communication bridges. Exceeding the cumulative wattage threshold will cause the unit’s thermal protection circuit to trip, shutting down the entire rack to prevent internal component damage. Additionally, ensure your ground wire terminates directly at the dedicated chassis grounding stud rather than daisy-chaining it through adjacent field devices, which can introduce ground loops.
Cross-Border Shipping and Customs Compliance
Transporting high-value control components across international boundaries requires precise trade documentation to avoid localized customs holds.
Export Controls and Commodity Classification
This industrial power supply component is subject to global export control verification. It carries an Export Control Classification Number (ECCN) of EAR99 and travels under the Harmonized System Tariff Code HS 850440. Every transaction undergoes automated denied-party screening prior to leaving our regional warehouses.
Logistics Framework and Incoterms
For critical assembly line stoppages, we utilize Priority International Air Express (via DHL, FedEx, or UPS), which maintains a 3 to 5 business day delivery window to major manufacturing centers worldwide. Delivery defaults to CIP (Carriage and Insurance Paid to Destination) per Incoterms 2020 definitions.
Import Clearance Requirement: Regional import tariffs, country-specific VAT/GST, and customhouse processing fees are not included in the baseline trade quote. The buyer’s designated customs broker must clear these costs with local tax authorities to facilitate seamless border clearance.
Frequently Asked Questions
Can this power supply be paired with another 1756-PA72 for a redundant power configuration?
No, the standard 1756-PA72 does not support parallel load sharing or redundant wiring configurations. If your system requires a redundant power architecture to prevent downtime, you must switch to a 1756-PA75R power supply paired with a 1756-CPR2 redundancy cable and matching adapter modules.
Does this module require manual configuration switches for 120 V AC vs 220 V AC operations?
No, the internal input circuitry is fully auto-ranging. The unit senses whether the incoming line supply is 120 V AC or 240 V AC and adjusts its internal switching frequencies automatically without requiring jumper changes or physical switch modifications on the terminal strip.
What do the front-panel LED indicators communicate during an error state?
The green status LED on the front face remains solid when the backplane outputs are within normal operating tolerances. If the LED turns off while input power is verified at the terminal strip, it typically indicates either an over-current condition on one of the backplane rails or an internal component failure.
What specific chassis size and module combination are you looking to power with this unit?
| Allen-Bradley 1734-IB8 |
| Rockwell 2198-D012-ERS3 |
| Allen-Bradley 80190-580-01-R |