Sale!

ABB DO815 (3BSE013258R1) S800 I/O Digital Output Module

Original price was: $2,090.00.Current price is: $2,000.00.

Parameter Value
Model Number DO815
ABB Part Number 3BSE013258R1
Output Type Digital Output / Transistor Current Sourcing (High-Side Driver)
Number of Channels 8 channels (Divided into 2 individually isolated groups of 4)
Rated Operating Voltage 24 V DC nominal (Acceptable supply spectrum: 10 to 32 V DC)
Max Continuous Current 2 A per channel (Max load capacity per module is constrained by MTU parameters)
Minimum Load Impedance < 0.25 \Omega internal on-state impedance
Category: SKU: DO815 (3BSE013258R1) Tag:

Description

The ABB DO815 (3BSE013258R1) is an 8-channel, 24 V DC high-current digital output module engineered for the S800 I/O distributed architecture within System 800xA and Freelance control systems. Operating as a current-sourcing (high-side) transistor driver array, it delivers up to 2 A of continuous current per channel. This makes it suitable for direct control of high-power industrial inductive loads—such as heavy-duty solenoids, hydraulic valves, contactor coils, and filament lamps—without requiring intermediate interposing relays.

 

Commercial and Availability Status

  • Product Condition: New Original (Factory Sealed / New Surplus) or Bench-Tested Refurbished/Exchange Units
  • Warranty: 12-Month Industrial Warranty
  • Estimated Lead Time: 1–3 business days (Global express dispatch)
  • Pricing Note: Unit pricing is subject to active factory lead times and spot market availability. Contact our parts desk for a firm, itemized commercial quote.

 

Technical Specifications

Parameter Value
Model Number DO815
ABB Part Number 3BSE013258R1
Output Type Digital Output / Transistor Current Sourcing (High-Side Driver)
Number of Channels 8 channels (Divided into 2 individually isolated groups of 4)
Rated Operating Voltage 24 V DC nominal (Acceptable supply spectrum: 10 to 32 V DC)
Max Continuous Current 2 A per channel (Max load capacity per module is constrained by MTU parameters)
Minimum Load Impedance < 0.25 \Omega internal on-state impedance
Isolation Groupwise galvanic isolation from system ground (50 V rated insulation)
Max Cable Distance 600 meters (656 yards)
Power Dissipation 4 W typical
ModuleBus Current Drop 120 mA typical (150 mA maximum) from +5 V DC rail
Maximum Filament Lamp Load 10 W per channel
Mechanical Keying Code AA
Dimensions 45 mm (W) × 102 mm (D) × 119 mm (H)
Weight 0.20 kg (0.44 lbs)
Environmental Hazard Certs G3 Conformal Coating (ISA-S71.04), Class I Div 2 cULus, ATEX Zone 2
Marine Class Approvals ABS, BV, DNV, LR

 

System Integration and Field Constraints

Advanced On-Board Diagnostics

The DO815 features hardware supervision mechanics per channel. It monitors open-loop and load faults on active channels, passing these flags up to the engineering workspace (e.g., Control Builder M).

  • Short-Circuit and Overload Protection: Built-in current limiting circuits dynamically clamp fault current if an external output is shorted to ground or positive supply.
  • Fault Operation Modes: The module supports two selectable runtime fault profiles:
    1. Automatic Reset Mode: Automatically attempts to re-engage the output switch once the physical overload thermal threshold cools down.
    2. Fault Latching Mode: Trips the internal electronic breaker upon detecting a fault condition, holding the channel off until software issues an explicit reset command.

Output Status Pattern (OSP) Execution

If communication with the parent controller (e.g., PM864 or CI801 ModuleBus cluster head) drops out, the onboard OSP logic activates. Rather than defaulting to unmanaged dropouts, the DO815 forces each channel into a predetermined, safety-cleared configuration (Hold Last Value, Force ON, or Force OFF) defined during structural system staging.

Termination Unit Selection

Mechanical Warning: The DO815 uses keying code AA. It must only be installed onto compatible Module Termination Units (MTUs) such as the TU810, TU812, TU814, or TU830. Forcing the module onto an incorrect backplane configuration will fracture the rear guide moldings.

Thermal Derating Constraints: When installing the module inside tight enclosures using a compact MTU configuration, the maximum allowable ambient thermal ceiling drops from +55 °C down to +40 °C if vertical mounting formats are selected. Ensure field panels maintain sufficient airflow or active fan extraction to prevent thermal tracking shutdowns under full 2 A channel saturation.

 

Frequently Asked Questions

Does the DO815 require flyback diodes when switching heavy inductive solenoid coils?

No. The DO815 incorporates high-capacity inductive load suppression components within its output block. However, if the field cable runs approach the 600-meter limit, adding an external flywheel diode right at the coil terminal box is a recommended field practice to clamp localized electromagnetic noise back-EMF.

What causes a channel fault LED to illuminate when the output command is active?

This usually points to an open-load threshold violation (load current dropping below the minimum active sensor floor), an external field wiring short-circuit to ground, or an undervoltage state on that specific isolated channel group’s 24 V DC external feed.

Can the DO815 be extracted or replaced while the remaining S800 I/O rack is active?

Yes. The module supports hot-swap operational behavior (Removal and Insertion Under Power). Provided your system is configured to permit Hot Configuration in Run (HCIR), pulling the module will only fault the specific I/O loop associated with this module’s slot without destabilizing upstream controller tasks. Ensure standard electrostatic discharge safety measures are practiced during field handling.

ABB DI890 (3BSE040134R1) S800 High Integrity Intrinsic Safety Digital Input Module
ABB DIS880 (3BSE078768R1) System 800xA Select I/O Safety Digital Input SCM
ABB PM864AK01 (3BSE018161R1) Original Controller Unit
ABB PFEA113-20 (3BSE0210058RD20) Tension Electronics