Description
1. At-A-Glance Executive Brief
- Model: 1KGT006600R0002 (560PSU01 R0002)
- Brand: ABB (Hitachi Energy)
- Part Type: Power Supply Unit (PSU) for RTU560 Racks
- Lifecycle status: Active / Maintained Substation Hardware
- Weight: 0.48 kg (Gross: 0.551 kg)
- Input Voltage: 110 … 220 V DC
- Output Voltages: 5.1 V DC and 24 V DC
2. Technical Introduction
Unstable auxiliary power or sudden voltage sags can cause mission-critical Remote Terminal Units (RTUs) to reboot, resulting in temporary telemetry loss across vital power transmission nodes. Maintenance personnel managing substation grid automation require robust, high-reliability power infrastructure capable of seamlessly supporting parallel redundancy. The ABB 1KGT006600R0002 (560PSU01 R0002) slides directly into RTU560 subracks (such as the 560SFR02 or 560MPR03), converting high-voltage DC feeds into tightly regulated 5V and 24V rails while supporting active load sharing for redundant configurations.
3. Core Technical Specifications
| Parameter | Value |
| Manufacturer | ABB / Hitachi Energy |
| Catalog Designation | 560PSU01 R0002 |
| Input Voltage Range | 110 … 220 V DC (-20% to +15%) |
| Output Rail 1 (U1) | 5.1 V DC (0.2 A to 5.5 A max) |
| Output Rail 2 (U2) | 24 V DC (0 A to 0.7 A max) |
| Power Output | 44.3 W |
| Physical Format | 3HE Eurocard format, 8R (40 mm) front panel |
| Backplane Connector | 48-pole type F DIN 41612 |
| Environmental Tolerance | Please refer to the OEM datasheet for complete environmental tolerances. |
4. Field Engineer’s Tech Notes
- Redundant Parallel Balancing: When configuring dual 560PSU01 units for redundant operation in high-availability subracks, ensure that both modules match exact rubric and firmware revisions. The units feature controlled load balancing, but mismatched versions can cause uneven thermal wear.
- Input Voltage Interruption Resilience: The module rides through short supply drops of up to 50 ms (at voltages >48 V DC). Verify that your station battery system’s upstream circuit breakers are sized appropriately to prevent nuisance tripping during minor auxiliary transients.
5. Adaptive QA & Testing Protocol
Our testing workflow for power supply units involves running each module on an automated electronic load bank simulating real-world RTU560 subrack draws. We verify regulation accuracy across both 5.1V and 24V output rails under step-load conditions, check ripple voltage parameters against strict factory thresholds, and test parallel load-sharing behavior. Full diagnostic test profiles and inspection certificates are available upon request.
6. Buyer’s FAQ
- Q: What warranty is included with this power supply unit?
A: All purchases include a standard 12-month replacement warranty covering structural and operational performance.
- Q: Are terminal blocks included with the module?
A: Yes, the unit ships with the necessary 3-pole pluggable screw terminal blocks (PKB type) for quick wiring of the DC input supply.
- Q: Is this part supplied as new surplus or refurbished?
A: Inventory status is precisely identified as New Surplus (NSFP) or factory-refurbished hardware; contact our sales team to verify current warehouse batch conditions.