Description
The Yokogawa F3PU10-0N is an AC input power supply module designed for the Yokogawa FA-M3 (Free and Multi-Abled) and FA-M3V programmable logic controller series. It mounts directly into the dedicated power slot of an FA-M3 base unit, converting line-voltage AC power into a regulated 5 V DC logic rail to drive the CPU, backplane communications, and attached I/O modules.
Technical Specifications
| Parameter | Value |
| Manufacturer | Yokogawa Electric Corporation |
| Product Type | PLC Power Supply Module |
| Model | F3PU10-0N |
| Input Voltage Range | 100 to 240 V AC (50/60 Hz); allowable range 85 to 264 V AC |
| Rated Output Voltage | 5 V DC (delivered via backplane bus) |
| Rated Output Current | 2.0 A |
| Power Consumption | 35 to 50 VA (maximum load dependent) |
| Allowable Power Hold-Up Time | 20 ms or more (maintains logic state during transient brownouts) |
| Isolation Method | Transformer isolation between primary and secondary terminals |
| Withstanding Voltage | 1,500 V AC for 1 minute between primary and secondary terminals |
| Operating Temperature | 0 to +55 °C |
| Enclosure Rating | IP20 |
| Dimensions | 28.9 mm (W) \times 100 mm (H) \times 83.2 mm (D) |
| Weight | Approximately 0.20 kg |
Commercial Terms & Availability
- Condition: New Original / Factory Sealed or Tested Surplus (verify current warehouse stock tier upon inquiry).
- Lead Time: 1 to 3 business days for standard stock items. Verify availability for project-batch quantities.
- Warranty: 12-month standard replacement warranty from the date of invoice.
- Pricing Note: Listed price is indicative and subject to current market conditions. Contact our engineering sales desk for a formal project quotation.
Engineering Context and Field Integration
When installing the F3PU10-0N within Yokogawa FA-M3 controller racks, system integrators must account for physical layout constraints and electrical protection requirements:
- Slot Allocation: This module is strictly designed for the leftmost dedicated power slot of compatible FA-M3 base units (such as the F3BU06-0N). It cannot be placed into standard I/O slots.
- Diagnostics & FAIL Output: The front panel features a status LED indicating a normal “Power OK” state. The unit also incorporates a hardware FAIL output contact that opens if the regulated 5 V DC rail drops below operational thresholds, providing a discrete signal for external emergency shutdown loops.
- Thermal Management: Maintain a minimum clearance of 50 mm above and below the base rack assembly. Natural convection cooling relies on unobstructed airflow across the module’s enclosure heatsink vents.
Frequently Asked Questions
Can the F3PU10-0N be hot-swapped during active system operation?
No. Hot-swapping the F3PU10-0N is strictly prohibited. Disconnecting or inserting the power supply module while AC mains voltage is applied will cause an ungraceful system crash, instantly dropping the backplane 5 V DC bus and halting CPU execution. Always isolate upstream power before servicing.
How does the module handle short circuits on the backplane?
The unit features built-in overcurrent and short-circuit protection. If a fault pulls down the 5 V DC rail, the internal protection circuit trips to prevent component damage. Once the external fault is cleared, the power supply recovers automatically without requiring physical fuse replacements.
Is this module compatible with DC-powered control panels?
No. The F3PU10-0N requires an AC input source (100 to 240 V AC). For 24 V DC-powered
| Yokogawa NFPW444 – I/O Module for Yokogawa CENTUM VP Control Systems |
| YOKOGAWA CP471-00 – CENTUM VP Processor Module |
| Yokogawa CP451-51 – Field Control Unit (FCU) Processor Module |