Sale!

Siemens 6ES7414-5HM06-0AB0 SIMATIC S7-400H Central Processing Unit

Original price was: $9,009.00.Current price is: $8,999.00.

Parameter Specification Value
Work Memory (Integrated) 4 MB total (2 MB for program code, 2 MB for data variables)
Load Memory (Plug-in) Expandable via external flash or RAM cards up to 64 MB
Processing Times 18.75 ns for bit operations; 37.5 ns for word arithmetic
Integrated Interfaces 1x MPI/DP (RS485), 1x PROFIBUS DP, 1x PROFINET (2-port RJ45 switch)
Redundancy Hardware 2x slots for optical sync submodules (up to 10 km separation)
Backplane Current Draw Max 1.6 A from the 5 V DC logic rail
Power Dissipation 6.5 W typical / 7.5 W maximum
Slot Requirements Occupies 2 standard slots on the S7-400 rack
Category: SKU: Siemens 6ES7414-5HM06-0AB0 Tag:

Description

The Siemens 6ES7414-5HM06-0AB0 is a high-availability fault-tolerant central processing unit designed for the SIMATIC S7-400H automation platform. This hardware serves as the primary processing node in redundant control architectures where process disruption risks catastrophic equipment damage or severe financial loss, such as in petrochemical processing, power generation, and pharmaceutical manufacturing.

Has a processor fault destabilized one of your redundant control loops? We hold physical inventory of this S7-400H processor in our regional logistics warehouse. This component ships within 24 to 48 hours of payment verification. Every unit includes a comprehensive 12-month replacement warranty that takes effect the day your maintenance team commissions the hardware on the plant floor.

Inventory, Warranty, and Logistics Summary

  • Unit Condition: New Original (Factory Sealed)
  • Availability: In Stock
  • Standard Lead Time: 1 to 2 business days worldwide
  • Warranty Period: 1 Year
  • Reference Price: Global supply chains for heavy industrial automation infrastructure fluctuate based on component availability and manufacturer release cycles. The listed price functions as a baseline market reference—contact our procurement team for a firm, itemized commercial quote.

 

Technical Specifications and Performance Parameters

Integrating an S7-400H controller requires balancing power budget allocations across the UR2-H segmented backplane rail. The CPU 414-5H incorporates a dedicated hardware synchronization interface, allowing it to mirror internal register states with a partner unit in real time.

Parameter Specification Value
Work Memory (Integrated) 4 MB total (2 MB for program code, 2 MB for data variables)
Load Memory (Plug-in) Expandable via external flash or RAM cards up to 64 MB
Processing Times 18.75 ns for bit operations; 37.5 ns for word arithmetic
Integrated Interfaces 1x MPI/DP (RS485), 1x PROFIBUS DP, 1x PROFINET (2-port RJ45 switch)
Redundancy Hardware 2x slots for optical sync submodules (up to 10 km separation)
Backplane Current Draw Max 1.6 A from the 5 V DC logic rail
Power Dissipation 6.5 W typical / 7.5 W maximum
Slot Requirements Occupies 2 standard slots on the S7-400 rack

 

Field Engineering Insights and Redundant Synchronization Rules

When deploying a pair of 6ES7414-5HM06-0AB0 processors in a high-availability arrangement, the physical arrangement of your fiber-optic synchronization links determines whether the system can achieve seamless bump-free bumpless transfer. Well, technically the system supports hot-swapping a failed processor while the process remains live, but only if your active unit is running in “Redundant” mode rather than “Solo” mode. If you see the Redundancy Lost (REDF) LED lit on the healthy processor, inserting the new CPU without verifying the firmware revision first can trigger an automatic master reset on both racks.

Pay close attention to the small slide switches located behind the front door panel that configure the card slot identification. One rack must be explicitly set as Rack 0, while the companion chassis must be set to Rack 1. In our experience, failing to match these physical slot switches with your hardware configuration layout compiled in STEP 7 V5.5 or TIA Portal V16+ causes a complete system initialization failure, marked by a solid EXTF (External Fault) indicator. Don’t underestimate the integrity of the optical sync modules (6ES7960-1AA06-0XA0)—even a tiny speck of dust inside the ceramic sleeve will degrade the optical link budget, causing the processors to fall out of step during heavy cyclic I/O updates.

 

Global Procurement and Customs Compliance Logistics

Incoterms and Transfer of Risk

We route international shipments under EXW (Ex Works) or FCA (Free Carrier) protocols from our major global logistics centers. For critical facility-down situations, we regularly arrange DAP (Delivered at Place) terms with global air express providers. Under DAP conditions, our logistics department manages all transit risks until the courier unloads the package at your facility gate.

Customs Tariffs and HS Code Classification

To bypass unnecessary border holds and administrative delays during international import processing, all shipping documentation carries the designated Harmonized System classification:

  • HS Code: 8537.10.91 (Programmable logic controllers for industrial automation control architectures)

Import fees depend on destination country policies. Orders sent to North American or European destinations may encounter specific regional administrative charges, while components routed into specific free-trade enterprise zones can bypass distinct import duties when accompanied by the correct Certificate of Origin documents prepared by our compliance specialists.

Commercial Trade Finance Protocols

Procurement departments can select from several approved payment frameworks based on internal risk management policies:

  1. Telegraphic Transfer (T/T): Direct bank-to-bank wire processing for immediate shipment dispatch.
  2. Letter of Credit (L/C): Documented credit facilities available for large-scale capital expenditure initiatives. We accept irrevocable letters of credit issued by prime international banks, payable at sight.

 

Frequently Asked Questions

Can this CPU operate as a standalone processor without a redundancy partner?

Yes. The CPU 414-5H can run as a high-performance standalone processor in a standard UR1 or UR2 rack. In this configuration, the optical sync slots remain unpopulated, and the processor operates in “Solo” mode. However, buying this specialized fault-tolerant module for non-redundant setups is rarely cost-effective unless you plan to scale up to an “H” system later.

What happens if the firmware versions do not match between the primary and backup CPUs?

The processors will refuse to enter the redundant operating state. When the primary unit attempts to copy its memory image to the backup processor over the optical synchronization links, it performs a firmware version check. If a mismatch is identified, the backup processor remains locked in “STOP” mode. You must use a memory card or the Simatic Manager hardware diagnostics interface to flash both processors to the exact same firmware revision before linking them.

Are the memory cards and synchronization modules included with the processor?

No. The 6ES7414-5HM06-0AB0 represents the base CPU module only. To build a functioning redundant station, you must order the external Flash or RAM memory cards, the target UR2-H rack, and two pairs of matching optical synchronization submodules with corresponding fiber patch cables as separate line items.

Siemens 6ES7417-4HL04-0AB0 – S7
Siemens6SE7027-2TD61-Z