Description
The ProSoft Technology PLX32-EIP-104 is an industrial protocol gateway designed to facilitate bi-directional data exchange between EtherNet/IP networks and IEC 60870-5-104 telecontrol systems.
In field integration environments, this module bridges Allen-Bradley/Rockwell Automation programmable automation controllers (PACs) or other EtherNet/IP devices with supervisory control and data acquisition (SCADA) systems, remote terminal units (RTUs), or distributed control systems (DCS) utilizing the IEC 60870-5-104 power utility protocol.
Technical Specifications
| Parameter | Value |
|---|---|
| Manufacturer | ProSoft Technology |
| Product Series | PLX30 Gateway Family |
| Model / Part Number | PLX32-EIP-104 |
| EtherNet/IP Protocol Support | Client (Class 3 PCCC/CIP) and Server (Class 1 I/O, Class 3 PCCC/CIP) |
| IEC 60870-5-104 Protocol Support | Server mode; supports up to 3 simultaneous client connections |
| Data Capacity | Up to 1,440 bytes input data and 1,440 bytes output data |
| Communication Ports | 2 x 10/100 Base-T, RJ45 Ethernet ports (supports dual subnet configurations) |
| Configuration & Diagnostics | Via Ethernet using ProSoft Configuration Builder (PCB) software |
| Storage Expansion | SD card slot (supports up to 32 GB for configuration storage) |
| Power Supply Voltage | 24 VDC nominal (10 to 36 VDC allowed) |
| Current Consumption | Approx. 300 mA at 24 VDC |
| Operating Temperature | −25 to +70 °C |
| Enclosure Protection | IP20 (DIN-rail mounted) |
Procurement and Availability
- Condition: New Factory Sealed / Surplus options available through industrial automation distributors.
- Lead Time: 1 to 3 business days for stock items; verify factory availability for project-scale quantities.
- Warranty: 12-month standard manufacturer or supplier warranty from date of shipment.
- Price: Indicative market pricing applies. Price subject to market conditions; contact us for a firm quote.
Integration and Compatibility Notes
The PLX32-EIP-104 acts as a modern drop-in enhancement replacement for legacy ProSoft gateways (such as the 5201-DFNT-104S module).
- Dual Ethernet Architecture: Features two independent Ethernet ports, allowing users to segment networks by running EtherNet/IP on one port/subnet and IEC 60870-5-104 on another, or combine both protocols on a single network interface.
www.prosoft-technology.com
- Migration path from Legacy Units: Configuration files from older 5201-DFNT-104S units can be directly imported and converted inside ProSoft Configuration Builder (PCB version 4.5.0.0 or higher) by modifying the module type.
www.prosoft-technology.com
- EDS Integration: Includes an embedded EDS add-on profile for simplified integration into Rockwell Automation Studio 5000 / RSLogix 5000 engineering environments.
www.mouser.com
Frequently Asked Questions
Q: Can the PLX32-EIP-104 initiate connections on the IEC 60870-5-104 side? A: No. On the IEC 60870-5-104 network side, the gateway operates exclusively as a server, accepting connection requests and commands from external client systems such as master SCADA stations.
Q: Is an SD card included with the gateway module? A: No. The SD card slot supports standard micro/standard SD cards (up to 32 GB) which are optional and used primarily for quick configuration backup, transfer, and offline storage.
Q: What software is required to set up communication parameters? A: Configuration, firmware updates, and real-time diagnostics are performed using ProSoft Configuration Builder (PCB) connected via the Ethernet port.