Description
The Beckwith Electric M-3311 (and its current iteration, the M-3311A) is a microprocessor-based, multi-winding protective relay engineered for utility and heavy industrial power transformers. Functioning as a comprehensive Integrated Protection System (IPS), this unit replaces multiple discrete legacy discrete components by consolidating phase differential, ground differential, overcurrent, and optional voltage/frequency monitoring into a single 19-inch rack-mount chassis. It is deployed on two-, three-, or four-winding power transmission and distribution transformers, as well as generator-transformer unit blocks.
Technical Specifications
| Parameter | Value / Detail |
| Model Platform | M-3311 / M-3311A |
| Supported Windings | 2, 3, or 4 independent winding inputs |
| Nominal AC Current Input | 1 A or 5 A rated CT options (specified at order) |
| Nominal AC Voltage Input | 60 V AC to 140 V AC secondary, 50/60 Hz nominal |
| Power Supply Options | 85 V to 260 V AC/DC or 24 V / 48 V DC configurations |
| Digital Inputs / Outputs | 6 programmable status inputs, 8 programmable output contacts |
| Measurement Accuracy | \pm 0.1 A or \pm 3\% for basic current metrics |
| Communications Suite | 2x RS-232 (Front/Rear), 1x RS-485 (Optional RJ45 Ethernet) |
| Network Protocols | MODBUS RTU, DNP 3.0, BECO 2200, IEC 61850 (variant dependent) |
| Enclosure Dimension | Standard 19″ Rack Mount (3U height); Depth: 10.2 in |
Standard ANSI Protective Functions
The M-3311 hardware layer executes an array of deterministic protection algorithms concurrently:
- 87T / 87H (Phase Differential & High-Set Instantaneous): Provides primary zone protection utilizing a dual-slope percentage restraint mechanism with selectable 2nd, 4th, and 5th harmonic cross-blocking to suppress magnetizing inrush and overexcitation tripping.
- 87GD (Ground Differential): Delivers sensitive restricted earth fault (REF) tracking for grounded star (Wye) windings, operating as a directional differential element.
- 49 (Winding Thermal Protection): Evaluates ongoing load currents against a programmable thermal time constant to calculate online winding degradation metrics.
- 50 / 51 / 50N / 51N / 50G / 51G: Comprehensive phase, residual, and neutral overcurrent protection matrices covering all inputs independently, featuring standard inverse, very inverse, extremely inverse, and specialized IEC/IEEE curve topologies.
- 50BF (Breaker Failure): Initiates backup isolation control upon local breaker restrike or stuck-contact scenarios.
Technical Features & Field Engineering Context
Phase & Vector Group Compensation
Unlike vintage analog protection schemes that mandate external interposing CTs to counteract vector phase shifts across Delta-Wye transformer configurations, the M-3311 manages this entirely within software. During 2 AM commissioning phases, field technicians must enter the specific vector group nomenclature (e.g., Dyn11) and individual CT ratios directly via the HMI interface or the IPScom software suite. The internal DSP dynamically scales magnitudes and corrects phase deviations internally.
Oscillographic Event Capturing
The onboard non-volatile memory automatically triggers transient oscillographic recordings upon an elements-trip flag or via external binary control inputs. It captures raw current and voltage waveforms at a high sampling rate, storing the records in COMTRADE format. Field engineers can utilize Beckwith’s IPSplot software to extract these captures, allowing the tracking of harmonic distribution, phase saturation levels, and exact millisecond breakdowns during an un-commanded trip event.
Communication & Protocol Integration Constraints
- MODBUS RTU Configuration: Remote supervisory systems connecting via RS-485 or RS-232 must map the dedicated holding and input registers outlined in the Beckwith Database Guide. Note that MODBUS RTU mode is strictly supported on designated COM ports (typically COM2/COM3) and remains fixed to an 8-data-bit, no-parity parameter envelope.
- Firmware & Software Matrix: Always verify the core firmware build version (e.g., D-0179 or later configurations) prior to flashing operational configuration files generated by different versions of the S-3300/IPScom utility tools, as mismatched profiles can result in memory mapping validation failure.
Commercial and Logistics Status
- Condition: Refurbished (fully bench-tested, secondary injected, and calibrated) or New Surplus.
- Warranty Period: 12-month operational protection hardware warranty from delivery date.
- Global Lead Time: Standard refurbished or surplus inventory configurations typically ship within 3 to 7 business days; verification of the specific CT input suffix (1 A vs. 5 A) is required before final dispatch.
- Documentation: Comprehensive parameter test sheets are issued with verified units; always cross-reference individual safety parameters with the formal OEM product instruction book.
Commercial Note: Market availability for the legacy M-3311 series exhibits variability due to generation updates toward the modern M-3311A platform. Listed pricing is indicative of general surplus values; contact our technical desk for a formal, project-specific commercial quote.
Frequently Asked Questions
Can an M-3311 model calibrated for 5 A CT inputs be reprogrammed via software to operate on a 1 A CT loop?
No. The CT input rating (1 A vs. 5 A) is dictated by the physical turns ratio of the internal analog matching transformers mounted to the internal printed circuit board. Altering this configuration requires changing physical hardware blocks or replacing the main analog processing board; it cannot be modified via software settings.
What is the function of the optional Voltage Protection Package?
When specified, the voltage package adds four additional elements: Overexcitation (24 V/Hz), Phase Undervoltage (27 for automated load-shedding control), Phase/Ground Overvoltage (59/59G), and Over/Underfrequency (81O/U) elements. Without this package, the relay relies purely on current inputs and operates strictly as a current/thermal unit.
How does the M-3311 execute a through-fault monitoring assessment?
The system continuously integrates phase current magnitudes during external faults that do not trigger the primary 87T zone. By calculating the accumulated I^2t I-squared-t thermal and mechanical stress envelope over time, it provides plant maintenance teams with predictive asset data regarding cumulative transformer winding deformation hazards.