Honeywell 05701-A-0361 System Control Module

Original price was: $6,877.00.Current price is: $6,788.00.

Parameter Specification
Manufacturer Honeywell Analytics (Zellweger Analytics)
Model Number 05701-A-0361
Series Series 57 Gas Detection System
Capacity Supports up to 4 individual 5701 input modules
Supply Voltage 24 V DC nominal (18 V DC to 32 V DC absolute input range)
Power Dissipation 2.5 W maximum (module logic only)
Relay Outputs 3 Common Alarm Relays (A1, A2, A3), 1 Fault Relay
Relay Contact Rating 5 A at 250 V AC / 30 V DC (non-inductive loads)
Communication Interface RS-485 / RS-232 engineering port for configuration software
Display Configuration Shared LED/LCD status indicators on rack front panel
Mounting Configuration Standard Series 57 19-inch rack or half-rack sub-chassis
Operating Temperature −10 to +55 °C (+14 to +131 °F)
Category: SKU: Honeywell 05701-A-0361 Tag:

Description

The Honeywell 05701-A-0361 is a 4-channel System Control Module designed for the Series 57 gas detection control architecture. This module provides centralized processing, display interface management, and common alarm relay outputs for up to four individual standard 5701 gas detection input cards. Operating as the master interface within a Series 57 rack assembly, the module monitors card status, manages the engineering interface serial connection, and provides global alarm outputs for industrial safety systems.

 

Commercial Availability & Procurement

  • Condition: New Original (New Surplus) or Refurbished (Fully Bench-Tested with gas simulator rigs)
  • Warranty: 12-Month Operational Warranty
  • Availability: Limited Stock (Legacy Product Line)
  • Estimated Lead Time: 2–5 business days via standard international air express
  • Pricing Policy: Price varies based on component revision level, current safety certification records, and market availability. Contact our technical sales division for a formal, binding quotation.

 

Technical Specifications

Parameter Specification
Manufacturer Honeywell Analytics (Zellweger Analytics)
Model Number 05701-A-0361
Series Series 57 Gas Detection System
Capacity Supports up to 4 individual 5701 input modules
Supply Voltage 24 V DC nominal (18 V DC to 32 V DC absolute input range)
Power Dissipation 2.5 W maximum (module logic only)
Relay Outputs 3 Common Alarm Relays (A1, A2, A3), 1 Fault Relay
Relay Contact Rating 5 A at 250 V AC / 30 V DC (non-inductive loads)
Communication Interface RS-485 / RS-232 engineering port for configuration software
Display Configuration Shared LED/LCD status indicators on rack front panel
Mounting Configuration Standard Series 57 19-inch rack or half-rack sub-chassis
Operating Temperature −10 to +55 °C (+14 to +131 °F)

 

System Integration & Real-World Field Constraints

Backplane Integration & Addressing

The 05701-A-0361 seats into a dedicated control slot on the Series 57 backplane assembly. It does not interface directly with field gas sensors; instead, it processes aggregated signal data from adjacent input cards via the backplane parallel bus.

Field Engineering Note: When configuring or replacing this card on a live backplane, verify that the hardware address jumpers or dip-switches match the exact matrix of the original unit. Incorrect address configuration will result in a global rack communication error, rendering the front panel display blank and triggering a system-wide fault relay condition.

Relay Contact Pitfalls

The internal common alarm and fault relays are dry contacts. While rated for 5 A resistive loads, running high-current inductive field devices (such as large warning sirens or heavy-duty visual beacons) directly through these micro-relays can pit or weld the contacts over time due to back-EMF spikes.

  • Best Practice: Always use external interposing relays or contactors to drive high-draw notification appliances.
  • Arc Suppression: Install appropriate RC snubbers across the external AC inductive loads, or flyback diodes across DC inductive loads to protect the internal 05701-A-0361 relay traces.

Legacy Configuration Constraints

System programming requires Honeywell’s legacy terminal configuration software interfacing via the serial engineering port. Many modern laptops lack native RS-232 COM ports. If you are troubleshooting a configuration at 2 AM with a standard USB-to-Serial converter cable, ensure the converter uses a high-grade FTDI chipset. Low-cost emulated chipsets often cause packet drops during configuration uploads, which can corrupt the module’s EEPROM and require a hard factory reset.

 

Frequently Asked Questions

What is the difference between the 05701-A-0361 and the standard 05701-A-0301 module?

The 05701-A-0361 is specifically optimized as a 4-channel control interface variant, typically used in smaller, localized half-rack enclosures or specific multi-point system layouts. The older or standard 05701-A-0301 is oriented toward alternative channel configurations. Mechanically they look nearly identical, but the internal firmware programming and backplane routing logic differ. Check your system’s original engineering schematic before interchanging these part numbers.

The module is showing a permanent “Fault” state immediately after power-up. How do I isolate the issue?

A persistent hardware fault LED generally points to one of three conditions:

  1. Supply Voltage Sag: Input power at the backplane terminals has dropped below 18 V DC under full load.
  2. Bus Misalignment: One or more of the attached 4-channel input cards is improperly seated or has a shorted input bridge, locking up the shared communication bus.
  3. EEPROM Checksum Error: The internal calibration or address memory has corrupted.

To isolate the fault, power down the rack, pull out all attached input cards, and boot the 05701-A-0361 alone. If the fault clears, re-seat the input cards one by one to locate the defective channel module.

Is this module hot-swappable while the gas detection system is active?

No. Standard operating procedure for the Series 57 platform dictates powering down the specific rack sub-assembly before extracting or inserting modules. Hot-swapping the control module can cause inductive tracking across the backplane edge connectors, potentially damaging the sensitive analog processing components on adjacent sensor input cards or causing accidental activation of emergency ESD (Emergency Shutdown) loops.